型号 | CXU /D _E | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 110 | 120 | 130 | 140 | 150 | 160 | 170 | 180 |
机组主要技术性能 | ||||||||||||||||
送风量 | m³/h | 9000 | 11520 | 15507 | 15840 | 16920 | 19440 | 23040 | 25200 | 25920 | 28080 | 28800 | 30960 | 33480 | 36000 | 38000 |
制冷量 | KW | 40.79 | 50.86 | 64.85 | 70.53 | 81.44 | 91.18 | 108.89 | 111.76 | 125.06 | 131.80 | 141.61 | 152.36 | 162.25 | 170.06 | 181.73 |
显热比 | 0.88 | 0.89 | 0.89 | 0.89 | 0.88 | 0.90 | 0.90 | 0.90 | 0.91 | 0.90 | 0.89 | 0.89 | 0.88 | 0.89 | 0.88 | |
制冷输入功率 | KW | 1.84 | 2.42 | 2.73 | 3.19 | 3.52 | 3.93 | 4.63 | 4.97 | 5.32 | 6.03 | 6.22 | 6.54 | 7.32 | 7.65 | 7.78 |
能效比 | 22.2 | 21.0 | 23.8 | 22.1 | 23.1 | 23.2 | 23.5 | 22.5 | 23.5 | 21.9 | 22.8 | 23.3 | 22.2 | 22.2 | 23.4 | |
冷冻水流量 | m³/h | 7.02 | 8.75 | 11.16 | 12.13 | 15.68 | 15.68 | 18.73 | 19.29 | 21.60 | 22.67 | 24.18 | 26.21 | 27.91 | 29.25 | 31.26 |
水阻力 | kPa | 68.2 | 82.7 | 102.8 | 93.3 | 80.1 | 84.3 | 120.2 | 110.1 | 102.5 | 120.3 | 104.3 | 94.7 | 107.3 | 89.4 | 96.7 |
通用配置 | ||||||||||||||||
风机型式 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | 无蜗壳风机 | |
风机数量 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 3 | 3 | 3 | 3 | 3 | 4 | 4 | |
风机输入功率 | kW | 1.84 | 2.42 | 2.73 | 3.19 | 3.52 | 3.93 | 4.63 | 4.97 | 5.32 | 6.03 | 6.22 | 6.54 | 7.32 | 7.65 | 7.78 |
加热量 | KW | 6 | 6 | 6 | 6 | 9 | 9 | 9 | 9 | 9 | 9 | 9 | 12 | 12 | 12 | 12 |
加湿量 | kg/h | 8 | 8 | 8 | 8 | 8 | 8 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 |
温度控制精度 | ℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ | ±1℃ |
相对湿度控制精度 | % | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% | ±5% |
注:1、机组的制冷量名义工况:室内回风干球温度24℃,相对温度50%(湿球温度17℃);冷冻水进出水温度7/12℃;
2、噪声为声压级,距机组3米处测得。
3、机组适应电源:3ph / 50Hz / 380V,电压波动范围±10%;控制器电源24V。